Wire size for a 16 amp EV charger

A 16 amp EV charger needs a 20 amp breaker: the NEC treats EV charging as a continuous load, so the breaker must be at least 125% of the charger’s current (625.41, 2023 NEC). On a short run, use 12 AWG copper THHN in conduit, 12 AWG copper NM-B (Romex) or 10 AWG aluminum.

Shop 16 A Level 2 chargers ↗ Shop 12 AWG THHN wire ↗

Wire size by distance

20 A breaker at 240 V, 16 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft12 AWG12 AWG10 AWG
50 ft12 AWG12 AWG10 AWG
75 ft12 AWG12 AWG10 AWG
100 ft12 AWG12 AWG10 AWG
125 ft10 AWG10 AWG8 AWG
150 ft10 AWG10 AWG8 AWG
200 ft8 AWG8 AWG6 AWG
250 ft8 AWG8 AWG6 AWG
300 ft6 AWG6 AWG4 AWG

Assumes a continuous load of of 16 A, the charger’s full output, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.

Check your own circuit

Hardwired or plug-in?

A charger that plugs into a NEMA 14-50 outlet is limited to 40 A on a 50 A circuit. The 16 A setting works hardwired or plugged in. Many chargers let you set a lower current, so you can install a smaller breaker and wire if your panel is short on capacity.

Other charger sizes

Breaker sizes