What size wire for a 200 amp breaker?

For a 200 amp breaker on a short run, use 3/0 AWG copper THHN in conduit, no NM-B cable (it isn’t made that large) or 250 kcmil aluminum. Longer runs need thicker wire: find your distance in the table below.

Shop 3/0 AWG THHN wire ↗

Wire size by distance at 240 volts

200 A breaker at 240 V, 160 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft—3/0 AWG250 kcmil
50 ft—3/0 AWG250 kcmil
75 ft—3/0 AWG250 kcmil
100 ft—3/0 AWG250 kcmil
125 ft—3/0 AWG250 kcmil
150 ft—3/0 AWG250 kcmil
200 ft—3/0 AWG250 kcmil
250 ft—3/0 AWG250 kcmil
300 ft—4/0 AWG300 kcmil

Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.

Check your own circuit

Can I use 2/0 AWG on a 200 amp breaker?

No. 2/0 AWG copper is too small: it is rated 175 A at 75 °C, which is less than 200 A. The wire must be rated at least as high as the breaker, or the wire can overheat before the breaker trips.