What size wire for a 90 amp breaker?

For a 90 amp breaker on a short run, use 3 AWG copper THHN in conduit, 2 AWG copper NM-B (Romex) or 2 AWG aluminum. Longer runs need thicker wire: find your distance in the table below.

Shop 3 AWG THHN wire ↗ Shop 2 AWG NM-B cable ↗

Wire size by distance at 240 volts

90 A breaker at 240 V, 72 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft2 AWG3 AWG2 AWG
50 ft2 AWG3 AWG2 AWG
75 ft2 AWG3 AWG2 AWG
100 ft2 AWG3 AWG2 AWG
125 ft2 AWG3 AWG2 AWG
150 ft2 AWG3 AWG2 AWG
200 ft2 AWG3 AWG1/0 AWG
250 ft2 AWG2 AWG2/0 AWG
300 ft—1 AWG2/0 AWG

Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.

Check your own circuit

Can I use 4 AWG on a 90 amp breaker?

No. 4 AWG copper is too small: it is rated 85 A at 75 °C, which is less than 90 A. The wire must be rated at least as high as the breaker, or the wire can overheat before the breaker trips.