Wire size for a 48 amp EV charger

A 48 amp EV charger needs a 60 amp breaker: the NEC treats EV charging as a continuous load, so the breaker must be at least 125% of the charger’s current (625.41, 2023 NEC). On a short run, use 6 AWG copper THHN in conduit, 4 AWG copper NM-B (Romex) or 4 AWG aluminum.

Shop 48 A Level 2 chargers ↗ Shop 6 AWG THHN wire ↗

Wire size by distance

60 A breaker at 240 V, 48 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft4 AWG6 AWG4 AWG
50 ft4 AWG6 AWG4 AWG
75 ft4 AWG6 AWG4 AWG
100 ft4 AWG6 AWG4 AWG
125 ft4 AWG6 AWG4 AWG
150 ft4 AWG6 AWG3 AWG
200 ft4 AWG4 AWG2 AWG
250 ft2 AWG3 AWG1 AWG
300 ft2 AWG3 AWG1/0 AWG

Assumes a continuous load of of 48 A, the charger’s full output, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.

Check your own circuit

Hardwired or plug-in?

A charger that plugs into a NEMA 14-50 outlet is limited to 40 A on a 50 A circuit. The 48 A setting requires the charger to be hardwired. Many chargers let you set a lower current, so you can install a smaller breaker and wire if your panel is short on capacity.

Other charger sizes

Breaker sizes