What size wire for a 45 amp breaker?

For a 45 amp breaker on a short run, use 8 AWG copper THHN in conduit, 6 AWG copper NM-B (Romex) or 6 AWG aluminum. Longer runs need thicker wire: find your distance in the table below.

Shop 8 AWG THHN wire ↗ Shop 6 AWG NM-B cable ↗

Wire size by distance at 240 volts

45 A breaker at 240 V, 36 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft6 AWG8 AWG6 AWG
50 ft6 AWG8 AWG6 AWG
75 ft6 AWG8 AWG6 AWG
100 ft6 AWG8 AWG6 AWG
125 ft6 AWG8 AWG4 AWG
150 ft6 AWG6 AWG4 AWG
200 ft6 AWG6 AWG3 AWG
250 ft4 AWG4 AWG2 AWG
300 ft4 AWG4 AWG2 AWG

Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.

Check your own circuit

Can I use 10 AWG on a 45 amp breaker?

No. 10 AWG copper is too small: it is rated 35 A at 75 °C and NEC 240.4(D) limits it to a 30 A breaker, which is less than 45 A. The wire must be rated at least as high as the breaker, or the wire can overheat before the breaker trips.