What size wire for a 20 amp breaker?

For a 20 amp breaker on a short run, use 12 AWG copper THHN in conduit, 12 AWG copper NM-B (Romex) or 10 AWG aluminum. Longer runs need thicker wire: find your distance in the table below.

Shop 12 AWG THHN wire ↗ Shop 12 AWG NM-B cable ↗

Wire size by distance at 240 volts

20 A breaker at 240 V, 16 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft12 AWG12 AWG10 AWG
50 ft12 AWG12 AWG10 AWG
75 ft12 AWG12 AWG10 AWG
100 ft12 AWG12 AWG10 AWG
125 ft10 AWG10 AWG8 AWG
150 ft10 AWG10 AWG8 AWG
200 ft8 AWG8 AWG6 AWG
250 ft8 AWG8 AWG6 AWG
300 ft6 AWG6 AWG4 AWG

20 amp circuit at 120 volts

20 A breaker at 120 V, 16 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft12 AWG12 AWG10 AWG
50 ft12 AWG12 AWG10 AWG
75 ft10 AWG10 AWG8 AWG
100 ft8 AWG8 AWG6 AWG
125 ft8 AWG8 AWG6 AWG
150 ft6 AWG6 AWG4 AWG
200 ft6 AWG6 AWG4 AWG
250 ft4 AWG4 AWG3 AWG
300 ft4 AWG4 AWG2 AWG

Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.

Check your own circuit

Can I use 14 AWG on a 20 amp breaker?

No. 14 AWG copper is too small: it is rated 20 A at 75 °C and NEC 240.4(D) limits it to a 15 A breaker, which is less than 20 A. The wire must be rated at least as high as the breaker, or the wire can overheat before the breaker trips.