Wire size for a 24 amp EV charger
A 24 amp EV charger needs a 30 amp breaker: the NEC treats EV charging as a continuous load, so the breaker must be at least 125% of the charger’s current (625.41, 2023 NEC). On a short run, use 10 AWG copper THHN in conduit, 10 AWG copper NM-B (Romex) or 8 AWG aluminum.
Shop 24 A Level 2 chargers ↗ Shop 10 AWG THHN wire ↗
Wire size by distance
| One-way distance | Copper NM-B | Copper THHN | Aluminum |
|---|---|---|---|
| 25 ft | 10 AWG | 10 AWG | 8 AWG |
| 50 ft | 10 AWG | 10 AWG | 8 AWG |
| 75 ft | 10 AWG | 10 AWG | 8 AWG |
| 100 ft | 10 AWG | 10 AWG | 8 AWG |
| 125 ft | 8 AWG | 8 AWG | 6 AWG |
| 150 ft | 8 AWG | 8 AWG | 6 AWG |
| 200 ft | 6 AWG | 6 AWG | 4 AWG |
| 250 ft | 6 AWG | 6 AWG | 4 AWG |
| 300 ft | 6 AWG | 6 AWG | 3 AWG |
Assumes a continuous load of of 24 A, the charger’s full output, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.
Check your own circuit
Hardwired or plug-in?
A charger that plugs into a NEMA 14-50 outlet is limited to 40 A on a 50 A circuit. The 24 A setting works hardwired or plugged in. Many chargers let you set a lower current, so you can install a smaller breaker and wire if your panel is short on capacity.
Other charger sizes
16 A charger32 A charger40 A charger48 A charger
Breaker sizes
15 A20 A25 A30 A35 A40 A45 A50 A60 A70 A80 A90 A100 A110 A125 A150 A175 A200 A