CircuitSizer

What size wire for a 150 amp breaker?

For a 150 amp breaker on a short run, use 1/0 AWG copper THHN in conduit, no NM-B cable (it isn’t made that large) or 3/0 AWG aluminum. Longer runs need thicker wire: find your distance in the table below.

Shop 1/0 AWG THHN wire ↗

Wire size by distance at 240 volts

150 A breaker at 240 V, 120 A load, max 3% drop
One-way distanceCopper NM-BCopper THHNAluminum
25 ft—1/0 AWG3/0 AWG
50 ft—1/0 AWG3/0 AWG
75 ft—1/0 AWG3/0 AWG
100 ft—1/0 AWG3/0 AWG
125 ft—1/0 AWG3/0 AWG
150 ft—1/0 AWG3/0 AWG
200 ft—1/0 AWG3/0 AWG
250 ft—2/0 AWG4/0 AWG
300 ft—2/0 AWG250 kcmil

Assumes a continuous load of 80% of the breaker unless you enter one, 75 °C-rated breaker and equipment terminals for THHN and aluminum (most modern breakers are marked 60/75 °C; check yours), and the 60 °C column for NM-B as NEC 334.80 requires. Shaded sizes were increased to keep voltage drop at or under 3%.

Check your own circuit

Can I use 1 AWG on a 150 amp breaker?

No. 1 AWG copper is too small: it is rated 130 A at 75 °C, which is less than 150 A. The wire must be rated at least as high as the breaker, or the wire can overheat before the breaker trips.

Other breaker sizes

EV chargers